In this scattered light smoke detector, the light emitter and receiver are arranged in the measuring chamber so that the light beam of the transmitter can not hit directly on the receiver. Only the light scattered on floating parts (smoke) (Tyndall effect) reaches the receiver and is converted into an electrical signal, which sets the detector in the alarm state and the built-in individual display lights up.
Already with a smoke quantity of 3% (according to EN 54-7), based on the optical scattered light principle of the smoke detector, the detector ensures an early and reliable opening of the respective smoke control dampers. As a result, the scattered light smoke detector offers a high degree of fire protection safety.
Scattered light smoke detector at a glance:
Matchcode | RM 3000 |
Article name | Optical smoke detector RM 3000 |
Part number | A3 2062 |
LED signs | Red = alarm |
IP code | IP43 |
Weight | 0.16 |
Housing | Plastic ABS |
Housing type | |
Colour | RAL 9010 |
Environment temperature range | -10 °C - 60 °C |
Part no. | Matchcode | |
---|---|---|
A3 2057 | RM/SCHUTZ | |
A3 2058 | PG | |
A3 2058 A | PG/RM 2860 | |
A3 2058 B | PG/RM 3000 | |
A3 2063 | RMS-3000 |
Optical smoke detector, type RM-3000
Optical smoke detector, tripping at 3% smoke (EN 54-7), voltage: 9 - 33 V DC, including mounting base, operating current at 30 V, alarm: 20 mA, operating current at 30 V, rest: 100 μA, alarm LED , ABS plastic housing white (RAL 9010), dimensions: Ø 100 mm, height 44 mm, protection class: IP 43, with VdS approval, test number: G 203036. Only detectors with VdS approval may be offered!
Brochure Control Panels | Brochure Control Panels |
Brochure smoke and heat detectors control | Brochure about control of smoke and heat detectors |
Catalogue (web) Smoke & Daily Vent | Catalogue (web) Smoke & Daily Vent |
0786-CPR-20042 | Declaration of consistency of performance |
DOP_32255_CT-3000-O_DE | Declaration of Performance RM 3000 |
Environmental Product Declaration (EPD) | Environmental Product Declaration (EPD) |