Part number | M2 1005 |
Input voltage | 24 V DC |
Nominal current | 0.5 |
Running speed | 5 |
IP code | IP54 |
Switch on duration | 30 |
The EA-L-450/300 is a linear actuator that is ideal for mounting on building coverings, e. g. B. inward and outward opening window, for installation and for the function in smoke extraction is suitable.
On the outside of the housing (anodized aluminum tube) is a multi-functional groove, which allows an invisible installation and flexible attachment of the connecting cable.
The actuator is housed in a special aluminum tube with integrated multifunction groove. A special shutdown with a current consumption of 0.5 A and a high running speed are also key advantages of this linear actuator. A high temperature resistance and continuous loadability are also natural. The integrated load shutdown prevents exceeding the current values ​​by switching off the actuator.
The linear actuator EA-L can be combined with the linear guide EA-LF-L. This allows a precisely guided and vertical lifting, z. B. of glass structures or roof elements. SIMON PROtec Systems offers the linear actuator EA-L-120 for mounting on louvre windows.
The advantages at a glance:
Matchcode | EA-L-450/300 |
Article name | Linear actuator EA-L-450/300 |
Part number | M2 1005 |
Input voltage | 24 V DC |
Nominal current | 0.5 |
Input voltage range | - 15 % / + 15 % |
Stroke | 300 |
Push force | 450 |
Pull force | 450 |
Nominal locking force | 1000 |
Cut-Off | eletronic and sequence signal |
Running speed | 5 |
IP code | IP54 |
Switch on duration | 30 |
Mounting way | attached |
Weight | 1.7 |
Housing | end-to end aluminum profile tube, anodized in EV1 |
Housing type | Aluminium |
Colour | On request |
Housing length | 663 |
Housing width | 36 |
Housing height | 42 |
Appliance class | III |
Connection cable | Silicone cable 3 x 0.75 mm², light gray, length 3,000 mm |
Nominal working temperature | 20 |
Environment temperature range | -5 °C - 75 °C |
Brackets included | no |
Linear actuator EA-L-450/300
24 V DC / 0.5 A / 450 N / 300 mm stroke
The linear actuator EA-L is an electromechanical actuator for opening and closing windows and flaps. The movement is linear via a spindle thrust tube. The actuator is located in an aluminum tube with an integrated multifunctional groove for individual fastening and concealed cable routing. The electronic load cut-off is integrated in the actuator and thus prevents overload in the end positions. End position detection and feedback via potential controlled F-contact. Tested according to DIN EN 12101-2 for smoke and heat ventilation applications. Special application with only 0.5 A nominal current for earlier control technology. No retriggering blockage!
Technical data:
Rated voltage: 24 V DC /±15%
Rated current: 0.5 A
Switch-on duration: 30% (ON: 3 min / OFF: 7 min)
Push force: 450 N
Pulling force: 450 N
Nominal locking force: 1000 N
Stroke length: 300 mm
Running speed: 5 mm/s
Protection class: IP54
Temperature range: -5°C to +75°C
Housing: aluminium profile tube anodized in EV1
Housing type: Aluminium
Connection cable: silicone cable 3 x 0.75 mm², light grey, length 3,000 mm
Dimensions (LxWxH): 663 x 36 x 42 mm
Sound level: < 70 dB (A)
Weight: 1.70 kg
Options:
- Coating according to RAL or DB
Manufacturer:
SIMON PROtec Systems GmbH
Type: Linear actuator EA-L-450/300
Article number: M2 1005
Brochure EA-L_Antriebsbroschuere | Actuator brochure for the linear actuator EA-L |
Brochure Window Automation | Brochure Window Automation |
Catalogue (web) Smoke & Daily Vent | Catalogue (web) Smoke & Daily Vent |
Technical details EA-L | Example for mounting of two linear actuators, Type EA-L, with various possibilities of mounting |
Technical details EA-L_GE | Examples for mounting for the linear actuator EA-L for bottom and top hung wings and combinations for the linear guiding |
Certifictate UKCA_EA-L_EA-LS | Declaration of conformity for linear actuators EA-L-xxx/xxx(-S), EA-L/S-xxx/xxx(-S) |
Environmental Product Declaration (EPD) | Environmental Product Declaration (EPD) |
Safety instructions and warranty conditions | Safety instructions and warranty conditions |