Unobtrusive, safe and durable: the fire curtain FireScreen 275-SFS-EW fulfills all the requirements that are placed on the room finish and the reduction of heat radiation. With its compact design and small dimensions, it fits in perfectly with existing room or building designs. Thus, the Fire Curtain Curtain FireScreen 275-SFS-EW is very well suited as a compensatory measure in fire protection.
The fire curtain FireScreen 275-SFS-EW is equipped with a smoke-proof and fireproof fabric (8 mm thick polyurethane coated fabric). The properties of the fabric reduce the heat radiation that can be caused by a fire and thus prevent ignition of distant objects and thus spreading the fire. For up to 90 minutes, the fire curtain reduces heat radiation (EW90) and provides a safe room closure for up to 120 minutes (E120).
A 230V electric motor with built-in electromagnetic brake keeps the fire curtain securely in place. In case of fire, the brake is released and the curtain closed by the gravity principle (gravity-fail principle).
The fire protection curtain FireScreen can also be seen optically or not. Due to its small dimensions, the fire curtain fits very well into existing room designs and comes to light only when triggered.
Advantages at a glance:
Matchcode | FIRESCREEN-275-SFS-EW |
Article name | Fire curtain FIRESCREEN-275-SFS-EW |
Part number | FSV 54101 |
Classification | E120 EW90 C2 according EN 13501-2 CE according EN 16034 |
Fabric | Polyurethane coated Fabric, 8 mm thick |
Unwind | Through Gravity (gravity fail safe) |
Rewind | Through integrated tube motor 230 V AC - end limits can be adjusted |
System installation | Ceiling or wall mounting with appropriate and verified material |
System size | max. 6000 x 4000 mm (WxH) |
Housing | Headbox: 275 x 275 mm (WxH); Side guides: 120 x 65 mm; Galvanized sheet steel |
Bottom Bar | Round bar as weight inside of the fabric |
Housing type |
Part no. | Matchcode | |
---|---|---|
A3 2054 | RM 2860 FSV | |
A3 2167 | HE-088-YELLOW-ALU | |
A3 2168 | HE-088-ORANGE-ALU | |
ST4 3604 | PROtec-RZ-24-230 | |
ST4 3605 | PROtec-RZ-24-230-SB | |
ST4 3608 | PROtec-RZ-24-230-SB-NA |
Fire protection curtain FireScreen EW90
The FireScreen EW90 fire curtain is classified for room closure for a duration of 120 minutes (E120) and for limitation of heat radiation for over 90 minutes (EW90). The FireScreen EW90 fire curtain is CE certified according to DIN EN 16034.
Head-box length: ___ mm
Clear width: ___ mm
Total height: ___ mm
Unroll length / Clear height: ___ mm
Classification: E 120 EW 90 C2 with CE according to DIN EN 16034
Fabric: Polyurethane coated fabric, 8 mm thick
Unrolling: by gravity (gravity fail safe)
Roll-up: By integrated 230 V AC tubular motor - end positions adjustable.
System mounting: Ceiling or wall mounting with suitable, approved mounting material.
System size (maximum): 8250 x 6000 mm (WxH); system width 8250 mm, unroll length 6000 m.
Housing: Head-box (W x H): Galvanized sheet steel 225 x 225 mm / 275 x 275 mm / 345 x 345 mm depending on clear opening.
End profile: Integrated round steel in fabric pocket for energy-free unrolling.
Side guide rails: Galvanized sheet steel 120 x 65 mm (W x H).
Manufacturer:
SIMON PROtec Systems GmbH
Type: Fire protection curtain FireScreen EW90
Identification (depending on system size and roll-off box): FIRESCREEN-225-SFS-EW / FIRESCREEN-275-SFS-EW/ FIRESCREEN-345-SFS-EW
Article number: FSV 54100 / FSV 54101 / FSV 54102
Brochure FSV + RSV | Brochure about the fire protection curtains and smoke protection curtains |
Installation manual Fire screen EW | Installation manual for the fire curtain Fire screen EW |
Operating Manual PROtec RZ-24 | Operating manual for the hold-open system PROtec RZ-24 for holding open and closing a textile fire curtain. |
Short instruction Service_button-RSV-FSV_EN | Short instruction for the service button for the smoke curtain and the fire curtain |
Supplementary sheet RSV + FSV | Supplementary sheet for smoke and fire protection curtains |
Technical details SFS-Winkel-Wand |
Certificate AM-830_DE-EN-FR_2016 | Certificate AM-830_DE-EN-FR_2016 |
Certificate_FireScreen_DE-EN-FR | Certificate for the fire protection curtain FireScreen |
Declaration of Performance - FireScreen - Draft | Draft Declaration of Performance with Declaration of Constancy |
Safety instructions and warranty conditions | Safety instructions and warranty conditions |